Top left
This page documents the top left configuration
Configuration file fields
This section is autogenerated from the Rule Schema file.
Sensor 1 (top-left) sensor.top_left
Type sensor.top_left.type
Thermocouple type
Type |
Default |
Options |
---|---|---|
integer |
3 |
B: |
Noise filter sensor.top_left.noise_filter
Line noise rejection filter. Select rejection of 50 Hz (EU) and its harmonics or 60 Hz (USA) and its harmonics
Type |
Default |
Options |
---|---|---|
integer |
0 |
50 Hz: |
Configuration explained
This section contains additional information and examples.
Type
The module internally performs a conversion from the thermocouple voltage measurement to temperature. To be able to do so, the module needs to know which type of thermocouple sensor is connected to the input port. Selecting the correct type of thermocouple type is crucial to get an accurate output result.
Note
The different thermocouple technologies each have specific properties such as temperature range and precision. The selection of thermocouples is beyond the scope of this documentation.
Noise filter
Long thermocouple cables pick up noise from a variety of sources, including AC power cables. To attenuate this input noise, the module includes a digital notch filter. The center frequency of the stop-band can be set to either 50 Hz (EU) or 60 Hz (USA).